Automatic Power Factor Controller, APFC, LCD, 3Ø, 12 Stage, built in-VAF- SELEC APFC148-312-90/550V-CE

13,093.00

Power Factor Controller with 3CT, 12 Stage, LCD Display, 90 to 550V AC, 144 x 144 mm size

Description

Description

Automatic Power Factor Controller, LCD, 3Ø, 12 Stage, built in-VAF- SELEC APFC148-312-90/550V-CE

  • Works for single and three phase systems
  • 12 stage programmable relay
  • Accuracy of ± 0.01 for power factor, ±0.5% for voltage and current
  • LCD display with dual colour backlite
  • Programmable PF: -0.8 to +0.8
  • Settable Parameters: Number of relays, step time, discharge time
  • NTC sensor to detect temperature of panel and Fan output to cool the panel
  • Alarm indications for Overcompensation, Under compensation, CT polarity error, Over temperature error, No voltage error
  • Auto and manual mode.
  • Wide Auxiliary supply: 90 to 550V
  • RS485 MODBUS RTU protocol

Brief Specifications

Display Type LCD with Dual Colour Backlight
Display Configuration 3 Lines of 4 Digits to Show Electrical Parameters
Input Type 3Ø-4 Wire, 3Ø-3 Wire, 2Ø-2 Wire, 1Ø-2 Wire
Frequency 45-65 Hz
CT Primary 1/5A to 9999A (Programmable for any Value)
CT Secondary 1 or 5 A (Programmable)
PT Primary 100V to 500kV AC (Programmable for any Value)
PT Secondary 100 to 500V AC (Programmable for any Value)
Accuracy Power Factor:±0.01, Voltage (L-N/L-L), Current: ±0.5% of full scale, Frequency – For L-N>20V, For L-L>35V: ±0.1% of full scale, Power (kW,kVA,kVAr), Energy (kWh,kVAh,kVArh): Class 1, Temperature : ±3° of full scale
Max Number of Steps 12/14* (FAN & ALARM Output Can be Used as 13th and 14th Step)
Communication Protocol Modbus RTU (RS485 Interface)
Supply Voltage 90 to 550V AC
Bezel Size 144 x 144mm
Mounting Type Panel Mount

 

Product Variations: 
Product Code Supply Voltage Certification
APFC148-312-90/550V-CE 90 to 550V AC CE, RoHS
APFC148-312-90/550V 90 to 550V AC
Additional information

Additional information

Brand

Selec

HSN Code

90328910